Analysis · Impulse Storm · October 2026
Degradation of the Foundations
The standard has become a register of names; the certificate, a reference to a report that does not exist
Standardisation and certification rest on two foundations. A standard is a requirement that can be verified independently of the seller. A certificate is evidence of a test passed before issue. In the condensed-aerosol class — pyrotechnic generators for total-flooding fire suppression — both foundations have been replaced: the standard by a register of names, the test by a verbal declaration, the approval by references to documents that do not exist. What follows is documents, and only documents.
0.8 % CO
at 100 g/m³ — US Coast Guard, 2006. Three systems, none met the protocol.
11,600 ppm CO
measured by the UK Health and Safety Executive, 2020. Data sheet: “less than 1,000”.
681.6 °C
at the discharge point — Transnet, South Africa, 2018. The fire was not extinguished.
3 names
hold the only numbers in NFPA 2010 for occupied spaces — numbers they wrote themselves.
1. A certificate resting on a non-existent report of a failed test
Bureau Veritas issued FirePro marine certificate No. 31670/C0 (expiry stated as 31 January 2028). The test basis in § 3.2 is “USCG R&D Center Final Report dated December 2005”. No such report exists. In 2026, in response to Freedom of Information requests, the US Coast Guard and the Defense Technical Information Center released the only document they hold: CG-D-03-06, dated February 2006. Its content: eighteen full-scale tests, three manufacturers, FirePro among them; none of the three systems met the protocol of the International Maritime Organization.
BSI issued FirePro UK certificate No. BSI/UK/3.46/560436 and entered the same report, by number — CG-D-03-06 — as its basis, together with an opinion:
The FirePro systems “passed all the tests and requirements … as reported by the USCG”.
The report says the opposite. The author of that opinion described himself in a letter filed in the US EPA federal docket on 24 July 2025: twenty-five years of work with FirePro, currently its contracted consultant.
The same pattern with Stat-X. In Bureau Veritas marine certificate No. 81824/A0 UK of 8 April 2026, the heading “Toxicity” lists two documents: the manufacturer’s own entry in the EPA list, made in place of a test laboratory, and the manufacturer’s own paper of 2014. Not a single test.
Verdict
Two certificates from two bodies — issued on a failure, rewritten by the manufacturer’s consultant.
2. A register instead of a standard
NFPA 2010 is not a standard. Its “Toxicity” section contains not one requirement with a number. The numbers sit in an informational annex, Table A.5.2.4: 100, 109.2 and 156 g/m³ — maximum densities for occupied spaces. Three numbers, three EPA codes: D, E, I. The public EPA table decodes them: D — Stat-X and Aero-K; E — FirePro; I — GreenSol. Everyone else gets an asterisk instead of a number: “If determined at a later date, a value could be added.” A vacancy notice in a register.
Who wrote the numbers. 100 — the maker of Stat-X, in its application to the EPA signed by the company’s president on 21 May 2013: “maximum standard design concentration is 100 g/m³”.
Who made the register mandatory. UL. Standard UL 2775, clause 6.8: design density “in accordance with NFPA 2010”. NFPA 2010, clause 4.2.1.2: compliance — with UL 2775. A closed loop: each document makes the other mandatory, and neither contains a criterion. UL Solutions confirmed this in writing on 6 August 2026:
“UL 2775 does not establish mandatory concentration limits”; the value is “not intended to serve as a toxicological threshold or human exposure limit”.
The condition for applying for certification — a named entry in the NFPA register called Standard 2010. Not one test is named as a condition.
Who checked. Nobody. The EPA runs no tests — by its own guidance the assessment is “based on information provided by the submitter”. The institute that allegedly produced the toxicological reports for both manufacturers (Hygiene-Institut des Ruhrgebiets, Gelsenkirchen) confirmed in writing in October 2025 that such tests were never within the scope of its accreditation.
Verdict
The value that admits people into a room was written by the manufacturer. The laboratory made it mandatory and itself called it a fire-performance figure. The agency accepted it without measuring. That is a register of names under the title of a standard.
3. The state measured — the manufacturers’ data sheets are inaccurate
USA, 2006. US Coast Guard, report CG-D-03-06: at 100 g/m³, carbon monoxide at 0.8 per cent — “significantly higher” than the level immediately dangerous to life.
Canada, 2014. Department of National Defence, report DRDC-RDDC-2014-C32: a Stat-X First Responder in the volume assigned by the manufacturer — nitric oxide peaking at 400 ppm, “in all cases” above the immediately dangerous limit. The manufacturer’s safety data sheet for the same product: 0.97. Its product sheet: “does not reduce the oxygen levels” — oxygen fell at every discharge.
South Africa, 2018. Transnet, port of Saldanha, report P.1225380: 681.6 °C at the discharge point of a fixed Stat-X generator. In test 3 the fire was not extinguished.
United Kingdom, 2020. The Health and Safety Executive (HSE): three FirePro generators — up to 11,600 ppm of carbon monoxide. HSE’s conclusion, verbatim:
“Regulatory bodies appeared to have accepted the manufacturer’s claims that CO production was low.”
Taken on trust. The manufacturer itself measured 2,400 at 100 g/m³ in 2021 — and on 22 December 2022 issued a safety data sheet stating “less than 0.1 vol%”, that is, less than 1,000. The data sheet was written after the measurement and contradicts it.
Finland, 2025. Emergency Services Academy Finland: a production FirePro unit bought on the open market, in the volume assigned by the manufacturer — over 8,000 ppm of carbon monoxide; measurements by an authorised organisation with calibrated instruments. The test was commissioned by the author of this article.
Verdict
Nobody in the approval chain measured. Everyone who measured found exceedances by tens and hundreds of times.
4. It kills without a fire
Resurgam, Newlyn, 15 November 2019. Installation of a FirePro system, unintended discharge, no fire. A twenty-year-old apprentice died. The state investigation, MAIB Report 9/2023, recorded the cause of death:
“Inhalation injury and carbon monoxide poisoning sustained following the discharge of an aerosol fire suppression system in an enclosed space.”
Bangkok, 13 March 2016: a Pyrogen system discharged during works in a bank vault — eight dead, no fire (AFP). Westerly, USA, 3 September 2020: unintended discharge in a school district’s server room, no fire — electrical arcing, “a thick layer of … dried paste” inside the equipment, everything replaced (official response of the district).
MCA Safety Bulletin 23 of 10 December 2021: a system “activated unintentionally and without warning or human input”; FirePro, Stat-X and MAG/Pyrogen named. Two discharges in 2019–2020 were never reported to the state investigator at all.
Verdict
A discharged generator is replaced only through the manufacturer’s authorised network — the count of discharges is kept by the seller, not by the state.
5. The insurer prohibited — the document permitted
FM Global, Data Sheet 5-32, January 2026, clause 2.4.1.4: aerosol systems are prohibited for data centers, related areas and electronic equipment. Grounds: not a clean agent; the effect of residue deliberately not investigated. Allianz Risk Consulting, 2022: corrosion damage to electronics at several Allianz clients.
NFPA 2010 knows this and says so itself: generators “can produce toxic levels” of carbon monoxide, nitrogen oxides and ammonia. And the same document permits occupied spaces — for three names from the table. The certifier did not investigate the residue and wrote so itself: UL’s category guide — “have not been investigated”; its market-surveillance findings it refused to disclose — “proprietary information”. The mark on the product nevertheless carries the word SAFETY.
Verdict
The insurer, who pays for what burns, prohibited. The document, which answers for nothing, permitted.
The bottom line
This is degradation of the foundations, and it is complete. The standard — a register of three names with numbers those names wrote themselves. The certificate — a reference to a report that does not exist, about a test that was failed. The approval — the manufacturer’s own entry in the list of an agency that does not measure, based on data that are kept secret. Measurements exist from every state that carried them out; none exist at any link that grants approval. That is how certificates are issued for products that kill without a fire.
The correction has begun. IMPULSE STORM has created a new concept of technical assessment for this class of products, now being developed jointly with a team of EU experts under the European state technical-assessment procedure pursuant to Regulation (EU) 2024/3110. In the Gulf states the same work is under way with national authorities. First results have been obtained; they will be reported when the procedures are complete. We expect to see the fire-protection market clean and transparent — a market where every number is backed by a measurement and every certificate by a test.
Valerii Ivanov